Weight | 0.92 kg |
---|---|
Product | LE1D09 |
Coil Voltage | P7 230 VAC Coil, V7 400 V Coil |
Conforms with | LRD01 – 14 Overload relays |
IP degree of protection | IP657 |
Height x Width x Dept | 166mm x 88mm x 128.5mm |
Utilisation category | AC-3 |
Cable entry | 2 x 13mm pg at bottom 2 x 16mm pg at bottom 2 x 20mm iso at bottom 2 x 20mm iso at top |
Note | The P7 230 VAC coil are suitable for single phase motors and the V7 400 V coil are suitable for 3 phase motors |
Overload relay selection | Please select the correct overload relay from the LRD01-14 range.To ensure the correct overload relay is selected check your motor name plate for its “full load current” .For example “full load current” states 6.2 amps,select the LRD12 (5.5-8A) overload relay. |